Ammonia Feed Control (Chloramination)

Statement of the Problem

Many utilities want to control a chloramination process by using existing chlorine residual analyzers in combinatin of with an analyzer able to detect free ammonia at trace concentration in the presence of chloramine. Up to the point of maximum monochloramine formation, a free ammonia residual will be present. This represents a fraction of the total ammonia present in the water, most of which is combined with chlorine. (For a more complete discussion, see the Application Summary entitled "Water Chloramination Process Control".)

Control Strategy

A 5 to 1 or less weight ratio of Cl2 to NH3-N will suppress the decomposition of monochloramine into dichloramine or trichloramine in water. If a modest free ammonia residual is maintained along with a target combined chlorine concentration after chloramine formation, the process can be maintained with chloramine concentrations near the monochloramine peak but not past this peak into the zone where chloramine decomposition begins to occur.

Apparatus

ChemScan® Process Analyzers can be used to detect free ammonia, while compensating for the presence of combined ammonia, turbidity and other chemicals. Spectrophotometric methods are used for the analysis. Expanded path length flow cells can also be used which are capable of detecting free ammonia at a fraction of a part per million, if desired.


Applications | Parameters | Product Selection | News
Why ChemScan | Technical Articles | Openings | Contact Us
Resources | F.A.Q. | Product Literature | Subscribe
Site Map | Search Our Site | Home Page

Applied Spectrometry Associates, Inc.
2325 Parklawn Drive, Suite I · Waukesha, WI 53186
Phone: 262-717-9500 · Fax: 262-717-9530
Toll Free: 800-665-7133
info@chemscan.com

Website production & hosting by onyourmark OnYourMark, LLC
Copyright © Applied Spectrometry Associates, Inc. All Rights Reserved | Privacy Statement